型 号 |
WSCZ210 (C) |
WSCZ240 (C) |
WSCZ300 (C) |
WSCZ350(C) |
WSCZ400 (C) |
WSCZ520 (C) |
WSCZ600 (C) |
WSCZ690 (C) |
WSCZ760 (C) |
WSCZ860 (C) |
||
R22 |
额定制冷量 |
kW |
213 |
243 |
304 |
346 |
398 |
522 |
600 |
687 |
763 |
859 |
额定输入功率 |
kW |
48.7 |
54.3 |
65.4 |
76.7 |
85.9 |
109.2 |
129.0 |
146.2 |
164.4 |
183.4 |
|
额定输入电流 |
A |
87.1 |
97.1 |
117.0 |
137.2 |
153.7 |
195.3 |
230.8 |
261.5 |
294.1 |
328.1 |
|
R407C |
额定制冷量 |
kW |
218 |
247 |
309 |
355 |
404 |
531 |
615 |
698 |
792 |
892 |
额定输入功率 |
kW |
49.8 |
53.9 |
68.6 |
78.0 |
85.4 |
114.1 |
130.6 |
145.2 |
166.4 |
181.7 |
|
额定输入电流 |
A |
89.1 |
96.4 |
122.7 |
139.5 |
152.8 |
204.1 |
233.6 |
259.7 |
297.7 |
325.0 |
|
使用电源 |
3Ph/380V/50Hz |
|||||||||||
压缩机 |
型 式 |
半封闭整体式螺杆压缩机 |
||||||||||
能量调节范围 |
0-50-75-100% |
|||||||||||
数量 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
||
制冷剂 |
节流方式 |
外平衡式热力膨胀阀/电子膨胀阀 |
||||||||||
R22充注量 |
Kg |
33 |
38 |
45 |
55 |
60 |
75 |
90 |
100 |
115 |
130 |
|
R407C充注量 |
Kg |
35 |
41 |
48 |
59 |
64 |
80 |
96 |
107 |
123 |
139 |
|
蒸发器 |
型 式 |
壳管式换热器 |
||||||||||
水流量(R22) |
m3/h |
36.6 |
41.8 |
52.3 |
59.5 |
68.5 |
89.8 |
103.2 |
118.2 |
131.2 |
147.7 |
|
水流量(R407C) |
m3/h |
37.5 |
42.5 |
53.1 |
61.1 |
69.5 |
91.3 |
105.8 |
120.1 |
136.2 |
153.4 |
|
进出水接管 |
mm |
DN114 |
DN114 |
DN114 |
DN114 |
DN168 |
DN168 |
DN219 |
DN219 |
DN219 |
DN219 |
|
水压降 |
kPa |
43 |
42 |
43 |
43 |
35 |
41 |
47 |
49 |
52 |
54 |
|
蒸发式冷凝器 |
型 式 |
高效板管蒸发式冷凝器(自主专利技术) |
||||||||||
冷凝排风量 |
m3/h |
22600 |
26000 |
33900 |
39000 |
45200 |
56500 |
65000 |
78000 |
78000 |
91000 |
|
排风机外静压 |
Pa |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
|
排风机功率 |
kW |
1.86 |
2.10 |
2.79 |
3.15 |
3.80 |
4.75 |
5.25 |
6.30 |
6.30 |
7.35 |
|
冷却水泵功率 |
kW |
2.2 |
2.2 |
3.0 |
4.0 |
4.0 |
4.0 |
5.5 |
7.5 |
7.5 |
7.5 |
|
耗水量 |
Kg/h |
288 |
328 |
410 |
467 |
537 |
705 |
810 |
927 |
1030 |
1160 |
|
外形尺寸 |
宽度 |
mm |
2530 |
2730 |
3520 |
4020 |
4520 |
5680 |
6580 |
7380 |
8280 |
9180 |
深度 |
mm |
1900 |
1900 |
1900 |
1900 |
1900 |
1900 |
1900 |
1900 |
1900 |
1900 |
|
高度 |
mm |
2160 |
2160 |
2300 |
2300 |
2300 |
2536 |
2536 |
2536 |
2536 |
2536 |
|
噪音 |
dB(A) |
69 |
70 |
71 |
72 |
74 |
75 |
76 |
79 |
80 |
82 |
|
重量 |
Kg |
2832 |
3098 |
3928 |
4295 |
4759 |
5855 |
6473 |
7028 |
7609 |
8175 |
备注:
1)额定制冷工况:冷冻水进/出水温度:12℃/7℃;室内排风干/湿球温度:27℃/19℃,室外新风干/湿球温度:35℃/28℃;
2)冷却水补水温度30℃;
3)用户可根据需要,调节室内排风负荷的回收比例,以获得健康的空调环境和最低的电力消耗。
4) 工作环境温度范围10℃~52℃.